APC Smart-UPS VT 20kVA 400V w/2 Batt Mod Exp to 4, Start-Up 5X8, Int Maint Bypass, Parallel Capable

APC Smart-UPS VT 20kVA 400V w/2 Batt Mod
Australian stock.Standard manufacturer's warranty for Australia applies. Please refer to the manufacturer's website for warranty details.
  • Our SKU #
    Manufacturer's #
  • 04417
    -
  • Manufacturer's #
  • SUVTP20KH2B4S

$16,929.42
Not in stock
By Order
Calculate Shipping Cost

APC Smart-UPS VT, 16 kW / 20 kVA,Input 400V 3PH / Output 400V 3PH, Interface Port DB-9 RS-232, Smart-Slot, Extended runtime model

Features

  • Parallel-capacity capable : Increases total power capacity by using multiple UPSs simultaneously.
  • Parallel-redundant capable : Power the connected equipment with multiple UPSs to increase system redundancy

Includes:

  • Battery modules ship installed, Bolt down brackets, CD with software, Installation guide, Network Management Card, Power modules ship installed, Start up included, User Manual
Output
Output Power Capacity 16 kW/ 20 kVA
Max Configurable Power 16 kW/ 20 kVA
Nominal Output Voltage 400V 3PH
Output Voltage Note Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage
Efficiency at Full Load 95%
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal
Crest Factor Unlimited
Waveform Type Sine wave
Output Connections (1) Hard Wire 4-wire (3PH + G) (1) Hard Wire 5-wire (3PH + N + G) (1) Screw Terminals
Bypass Built-in Maintenance Bypass,Built-in Static Bypass
Input
Nominal Input Voltage 400V 3PH
Input Frequency 40 - 70 Hz (auto sensing)
Input Connections Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations 304 - 477V
Other Input Voltages 380,415
Maximum Input Current 27A
Input Breaker Capacity 50.0  A
Batteries & Runtime
Battery Type VRLA
Included Battery Modules 2
Available Battery Slots 2
Typical recharge time 4 hour(s)
RBC™ Quantity 2
Nominal Battery Voltage +/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage +/-154 V
Extended Run Options APC Smart-UPS VT 20kVA 400V w/2 Batt Mod Exp to 4, Start-Up 5X8, Int Maint Bypass, Parallel Capable
Communications & Management
Interface Port(s) DB-9 RS-232,Smart-Slot
Pre-Installed SmartSlot™ Cards AP9631
Control panel Multi-function LCD status and control console
Audible Alarm Audible and visible alarms prioritized by severity
Emergency Power Off (EPO) Yes