APC MGE Galaxy 3500 40kVA 400V 3:1, Start-up 5X8

APC (G35T40K3IS) MGE Galaxy 3500 40kVA 400V 3:1, Start-up 5X8
Australian stock.Standard manufacturer's warranty for Australia applies. Please refer to the manufacturer's website for warranty details.
  • Our SKU #
    Manufacturer's #
  • 28393
    -
  • Manufacturer's #
  • G35T40K3IS

$18,152.63
Not in stock
By Order
Calculate Shipping Cost

APC MGE Galaxy 3500 UPS - supplied without batteries. To be used with either external third party battery system, or with internal long life modular batteries (SYBTH4).

Specifications

Output
Output Power Capacity 32 kW/ 40 kVA
Max Configurable Power 32 kW/ 40 kVA
Nominal Output Voltage 230V
Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load 95.4%
Output Voltage Distortion Less than 5%
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal
Other Output Voltages 220, 240
Crest Factor Unlimited
Topology Double Conversion Online
Waveform Type Sine wave
Output Connections (1) Hard Wire 3-wire (H N + G) (1) Screw Terminals
Output Voltage Tolerance +/-1% static and +/- 5% at 100% load step
Output Voltage THD
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Efficiency at Half Load 95.5%
Required Output Current Protection 200A
Bypass Built-in Maintenance Bypass, Built-in Static Bypass
Input
Nominal Input Voltage 400V 3PH
Input Frequency 40 - 70 Hz (auto sensing)
Input Connections Hard Wire 5-wire (3PH + N + G)
Input voltage range for main operations 340 - 460 (400V)V
Input voltage adjustable range for mains operation 340 - 460 (400V)V
Other Input Voltages 380, 415
Maximum Input Current 54A
Input Breaker Capacity 63  A
Input Total Harmonic Distortion Less than 5% for full load
Type of Input Protection Required 3-pole breaker
Batteries & Runtime
Battery Type No internal battery supplied with UPS - can be used with external third party batteries or SYBTH4
Nominal Battery Voltage +/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage +/-154 V
Overload Operation 10 minutes @ 125% and 60 seconds @ 150%
Extended Run Options MGE Galaxy 3500 40kVA 400V 3:1, Start-up 5X8

Includes:

  • Bolt down brackets, Installation guide, Network Management Card, Power modules ship installed, Smart UPS signalling RS-232 cable, Start-Up Service, User Manual